Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
198
Manual, 04.2016, A5E35883207-7-76
Slot
Subslot Data
Description
Value range
Data size
Channel2 Ithreshold
Channel2 Output
Enable
Channel2 Reset_In
Data block active
1-6
4
Channel3 Utarget
[10 mV]
see data "Channel 1"
Channel3 Ilimit
[10 mA]
Channel3 Ithreshold
Channel3 Output
Enable
Channel3 Reset_In
Data block active
1-6
5
Channel4 Utarget
[10 mV]
see data "Channel 1"
Channel4 Ilimit
[10 mA]
Channel4 Ithreshold
Channel4 Output
Enable
Channel4 Reset_In
Data block active
7.6.1.3
Operating states SITOP PSU8600
Operating state of the power supply system (device operating state)
Status message
Description
0 = Off
Power supply system is switched off
1 = ErrorOff
The power supply system was automatically shut down as a result of operation under in-
admissible operating conditions.
2 = CooledDown
After an automatic shutdown due to a fault, the power supply system can be reactivated by
switching off and switching on the supply voltage.
3 = Boot
The power supply system is powering up, all of the outputs are still switched off.
4 = Running
The power supply system is operating in the normal mode.
5 = Phasefail
Phase failure of the supply voltage detected. The power supply system can continue to
operate in the normal mode without any restrictions for a limited period of time.
6 = SystemOverload (IP)
System overload detected within the permissible overload profile. The power supply system
is still operating in the normal mode.
7 = SystemOverload (OP)
System overload detected outside the permissible overload profile. Power supply system
only operating with some restrictions.
8 = SystemOverload (PL)
Very high, brief load peak detected. Power supply system is operating in the normal mode.
9 = Buffering
Primary supply voltage has failed. Power supply system is operating in the buffer mode.
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...