Operator control at the device
3.8 Connecting outputs of the basic unit in parallel
PSU8600power supply systems
70
Manual, 04.2016, A5E35883207-7-76
Deactivating the parallel connection of the outputs
With the power supply shut down, bring the corresponding DIP switch "P1+2" (outputs 1 and
2) or "P3+4" (outputs 3 and 4) into position "OFF" (left), to deactivate the parallel connection.
P1+2
or
P3+4
After they have been switched-on again, the outputs are in the operating state "Manually
shut down" (LED of the outputs are lit yellow). You can switch-on the outputs again by
pressing the appropriate button.
Activating the parallel connection of the outputs
With the power supply system shut down, bring slider switches "P1+2" (outputs 1 and 2) or
"P3+4" (outputs 3 and 4) in position "ON" (right) to activate the parallel connection.
P1+2
or
P3+4
The LEDs with the designation "Parallel", assigned to the relevant outputs, are lit green.
After switching on again, the output connected in parallel is in the operating state "manually
shut down" (LED "ON/OFF/RST" of output 1 or 3 is lit yellow). You can switch-on the output
again by pressing the appropriate button.
Values for output voltage and response threshold value of the output current when the parallel
connection is activated
The potentiometer for output 2 is deactivated when connecting outputs 1 and 2 in parallel.
The common output has the output voltage defined using the voltage potentiometer for
output 1.
The valid response threshold value of the output current is obtained by doubling the setting
value at the current potentiometer of output 1.
Example: A setting value of 8 A results in a response threshold value of 8 A x 2 = 16 A.
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...