Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
212
Manual, 04.2016, A5E35883207-7-76
Index 0x0021: Buffer state information (reading)
Data
Description
Data type
Buffering disabled by inputs [0/255]
Buffer component was deactivated via the control
contact.
Unsigned8
Buffer ready (0/255)
Buffer component ready for buffering.
Unsigned8
Charging state (0-100 %)
Charge state of the buffer module.
Unsigned8
Fill byte [s]
-
Unsigned8
Index 0x0030: PROFIenergy values (reading / writing)
Data
Description
Data type
PROFIenergyEnabled (0/255)
Enable PROFIenergy on this device
Unsigned8
Fill byte [s]
-
3xUnsigned8
Time_To_Pause [ms]
-
Unsigned32
Time_To_Operate [ms]
-
Unsigned32
Minimum_Stay [ms]
-
Unsigned32
Maximum_Stay [ms]
-
Unsigned32
Saving_Power_Consumption [kW]
-
Float
Operate_Power_Consumption [kW]
-
Float
Energy_Consumption_To_Pause [kWh]
-
Float
Energy_Consumption_To_Operate [kWh]
-
Float
Index 0x0031: PROFIenergy channel list (reading/writing)
Data
Description
Data type
ChannelsOffList
Overview of the outputs that are shutdown. Each
output is represented using 1 bit (starting with bit 0
for output 1).
Unsigned32
Index 0x0035: Web server (reading/writing)
Data
Description
Data type
WebserverEnabled
Activating/deactivating the web server of the
SITOP PSU8600:
•
0: disable
•
255. enable
Unsigned8
AutoReloadEnabled
Enable/disable automatic update:
•
0: disable
•
255. enable
Unsigned8
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...