Description, device design, dimension drawing
2.6 Displays
PSU8600power supply systems
36
Manual, 04.2016, A5E35883207-7-76
States of the individual LEDs
Table 2- 12 LED "OK"
①
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation, module charged, complete buffer readiness
Flashing green (1/1)
Module is being charged, buffer readiness partially available.
Flashing green (0.25/0.25)
Module is being charged, buffer readiness not available
Red
•
ERROR OFF: Module automatically shut down due to overtemperature basic
device, phase dissymmetry
•
Fault in the device or communication error to the basic device
flashing red (1/1)
Module deactivated via ON/OFF contact or remote command (no buffering when
the power fails)
Flashing red (0.25/0.25)
•
Device ready for the automatic ERROR OFF shutdown to be reset – or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
•
Charge is still available after power supply voltage OFF
•
Device shut down due to firmware update of another system component
•
Incorrect hardware configuration (REMOTE mode)
Yellow
Power failure, buffer mode active
Alternating, green/red
(0.25/0.25)
Firmware being updated
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...