Description, device design, dimension drawing
2.4 Connections and terminal designations
PSU8600power supply systems
22
Manual, 04.2016, A5E35883207-7-76
Terminal data 6EP3437-8MB00-2CY0:
*1) Do not subject the end stop to high loads
Ethernet/PROFINET connection
Maximum length of the Ethernet/PROFINET cable: 100 m (90 m BASIC link plus 2 x 5 m
CHANNEL link).
The interface corresponds to the standard full duplex up to 100 Mbit/s electrical (100BASE-
TX) according to IEEE 802.3.
Properties of the interface:
●
Transfer rate 10/100 Mbit/s
●
Two RJ45 sockets, i.e. integrated switch, for RJ45 connector, cable type 100Base-TX
(CAT5)
●
Auto negotiation
●
Auto crossover communication via TCP/IP and PROFINET
The physics of the Ethernet/PROFINET interface are implemented so that PROFINET IO
according to standards IEC 61158 and IEC 61784-2 are possible. As a minimum, conformity
Class B is maintained for PROFINET.