PSEL-3000-2

Troubleshooting Guide

Symptom

Possible Cause

Solution

No voltage present on any of the 

output terminals

No AC input power present

Check AC input power

115VAC 60Hz / 6.3amp 

Green AC Power LED indicates 

115VAC present

Electric lock does not attempt to 

unlock after input trigger

And no input LED response  

Factory installed fire alarm jumper missing 

or open circuit on fire alarm control circuit

FAI (Fire Alarm Interface) LED will 

illuminate green when fire alarm circuit 

activated

If no FACP integration required for 

system, install jumper wire across FACP 

and GND terminals

If FACP control is required then 

connect NC “DRY” contacts to FACP 

and GND terminals

Locking devices remain unlocked 

when no activation trigger given

Fire alarm circuit activated and dip switch 

SW-4 in off position

FAI / IN1 / IN2 LED’s illuminated

Ensure that activation circuit is 

connected to a “DRY” (no voltage 

present on circuit) NO set of contacts 

from activation device (access system, 

push button, key-switch, etc.)

Verify wire integrity on circuit by 

disconnecting input trigger wires and 

using jumper wire to activate panic 

device power controller 

Input trigger/activation circuit improperly 

configured or direct short in activation 

circuit

IN1 / IN2 LED’s illuminated

If no FACP integration required for 

system, install jumper wire across 

FACP and GND terminals

If FACP control is required then 

connect NC “DRY” contacts to FACP 

and GND terminals

Locking devices do not respond to 

input trigger activation but input 

LED indicators respond by blinking

Open or short circuit condition on 

controller output circuit

Slow blinking input LED  indicates open 

condition on output circuit to electric 

locking device

Rapid blinking LED indicates direct short 

condition on output circuit to electric 

locking device

IN1 and/or IN2 blinking slowly or 

rapidly indicates problem with output 

circuit wiring to load 

Verify wire integrity on controller 

output circuit by disconnecting/

bypassing existing output wiring and 

running new temporary wires from 

power controller to locking device 

SEE WIRE DISTANCE CHART