Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
206
Manual, 04.2016, A5E35883207-7-76
Data
Description
Data type
Parallel mode 34 DipSwitch (0/255)
Actual switch position for parallel switch-on (P3+4)
of output 3 and output 4 at the basic device
SITOP PSU8600.
Unsigned8
Webserver Enable DipSwitch (0/255)
Actual switch position for activating/deactivating
the web server.
•
0 = web server deactivated
•
255 = web server activated
Unsigned8
Reset_In-Input (0/255)
Status of input "Reset_In": This input resets all
active faults and reactivates all of the outputs that
are in the "Ready for restart" operating state.
Unsigned8
Utarget1 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit1 potentiometer [10mA]
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable1 manual button (0/255)
Actual DIP switch state for output 1:
•
0 = Manually shut down
•
255 = Manually switched on
Unsigned8
Fill byte[s]
-
Unsigned8
Utarget2 potentiometer [10 mV]
Manually set setpoint of the output voltage at out-
put 2: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit2 potentiometer [10 mA]
Manually set threshold of the output current at
output 2. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable2 manual button (0/255)
Actual DIP switch state for output 2:
•
0 = Manually shut down
•
255 = Manually switched on
Unsigned8
Fill byte[s]
-
Unsigned8
Utarget3 potentiometer [10 mV]
Manually set setpoint of the output voltage at out-
put 3: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...