Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
121
DC2-026-2.07, Edition 10.2016
2.6.2.3 Settings for Priority Signals
Create priority signals which will act as the output signals in the logic as follows. The signal
name must be numerical.
2.6.2.3.1 Output Link of CAEx plus
After creating the priority signals, select LNK_CAExplus and make necessary changes for
configuring as CAEx
plus
output link.
Select the parameter
Lk_Cat
as
IEC-standard
via the relevant pull-down menu.
Select the parameter
Lk_Prep
as
Activated
via the relevant pull-down menu.
All other signals will be updated automatically.