Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
119
DC2-026-2.07, Edition 10.2016
2.6.2.1 Settings for Communication Fault
2.6.2.1.1 1703 System Link
After creating the signals, select LNK_1703_SYS and edit the required values for configuring
as an input signal.
Select the parameter
Lk_Reg
and
Lk_Comp
via the relevant pull-down menu.
Select the parameter
Lk_Cat
as
Error message sum diagnostics table
via the relevant pull-
down menu.
Enter the value for the parameters
CASDU1
and
CASDU2
value same as provided in the web
parameterization of CP-6010.
Enter the value for the parameters
IOA1
,
IOA2
and
IOA3
according to the plant address
concept. The value must not be included in the list provided in the Appendix
Select the parameter
Error_location/BSE
to
C1-CPU
. You can also select any configured
BSE values via the pull-down menu.
Select the parameter
Error_location/SSE
to
PRE1
. You can also select any configured
SSE values via the pull-down menu.
Select the parameter
Error_type
to
Communication Fault
. You can also select any
configured error type via the pull down menu.