Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
113
DC2-026-2.07, Edition 10.2016
2.5.3
Example of Line-by-Line Switchover
2.5.3.1 System-Technical Settings
In both systems SICAM AK, select the menu
Redundancy
under the M-CPU.
Select the parameter
Redundancy control
as
Line. redundancy switchover with appl.
voting
via the relevant pull-down menu. This enables the device to apply the “line-by-line
switchover”.
Under
Settings for PREs
, select the PRE on the M-CPU (connected to the voter) as
Active
via the parameter
Option: preferred position
and select the
User data filter
deactivated
via the parameter
Option: user data filter deact
.
All the other PREs are selected as
Passive
via the parameter
Option: preferred
position
.
Copy all the parameters from SICAM AK A to SICAM AK B and change the IP address of
SICAM AK B.