Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
115
DC2-026-2.07, Edition 10.2016
2.5.3.2.1 Control Message from CP-6010 to SICAM AK
Select the values for the parameters
Lk_Reg
and
Lk_Comp
via the relevant pull-down menu.
Select the parameter
Lk_Cat
as
Redundancy control message
via the relevant pull-down
menu. This represents the control signal from CP-6010 to SICAK AK A.
Enter the same values for the parameters
CASDU1
and
CASDU2
value as provided in the web
parameterization of CP-6010.
Enter the values for the parameters
IOA1
,
IOA2
and
IOA3
for the module as provided in
Configuration for CP-6010 to SICAM AK
(for
C1-CPU
, IOA values are
IOA1
=
68
,
IOA2
=
0
,
IOA3
=
0
).
Select the following values via the relevant pull-down menu:
─
Control function_(RED)
as
A/P-control
─
BSE_(RED)
as
C1-CPU
; change the value depending on the desired BSE
─
PRE_(RED)
as
BSE itself
; change the value depending on the desired PRE
─
Priority_(RED)
as
Priority 0 (lowest)
Afterwards click on
Save
.
Note
For the parameterization of further control signals, proceed as previously described.
For the configuration of SICAM AK B, proceed according to the same procedure as for SICAM AK A.
The following values must be updated in the SICAM AK B:
•
Region
•
Component
•
CASDU