Redundancy via CP-6010
120
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
2.6.2.1.2 CAEx plus Link
After creating the signals, select LNK_CAExplus and make the following changes.
Select the parameter
Lk_Cat
as
IEC-standard
via the relevant pull-down menu.
Select the parameter
Lk_Prep
as
Activated
via the relevant pull-down menu.
All the other signals will be updated automatically.
2.6.2.2 Settings for Communication Board Failure
For the signal
Communication board failure
, you can copy the already configured
Communication fault
parameters.
After copying, update the
IOA
and
Error_type
in the LNK_1703_SYS.