Redundancy via SCA-RS
SICAM RTUs, SICAM AK Redundancy
Unrestricted
55
DC2-026-2.07, Edition 10.2016
1.3.2.3 Settings for BSEs (AU Redundancy)
In the OPM system technique you have selected
Redundancy control
under the node
Redundancy
below the M-CPU and chosen the following entry in the
Value
dropdown list:
Line-by-line redundancy switchover with SCA-RS
•
Select
Settings for BSEs (line. red. w. SCA-RS)
:
Settings for BSEs (line-by-line redundancy switchover with SCA-RS)
Column
name/Parameter
Description/Value
Comment
Priority assignment
Defines, for which SEs the priorities should be
valid after the occurrence of an error
The affected systemelement:
The affected BSE and its PRE
:
All systemelements:
Option: switchable
Defines, whether the voter should switchover the
defined BSE (
System element is being switched to
passive
) or not (
Systemelement is not being
switched to passive
)
The parameter is valid for
the selected BSE. The PE
(if available) is switched
passive indirectly: the filter
acts in the direction of the
PE, the data from the PE
are flagged with R-Bit.
In the OPM system technique you have selected
Redundancy control
under the node
Redundancy
below the M-CPU and chosen the following entry in the
Value
dropdown list:
Line-by-line redundancy switchover with application-related voting
•
Select
Settings for BSEs (line. red. w. appl. voting)
: