Redundancy via CP-6010
108
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
Note
The value of
number of APDUs until acknowledgement (w)
must be set to
1
. All other parameters of
IEC 60870-5-104 have default values.
Select the menu
Topology
and select the
SID-ST
value via the relevant pull-down menu.
This is required to define the connection between SICAM AK and voter. The station number
specified in the connection definition must be selected to define the topology.
For the “line-by-line switchover”, add the basic system elements (BSE) which are used in the
system.
The following figure provides an example on how C1-CPU is used in the configuration with the
M-CPU.
Note
If you have a different configuration (BSE) in SICAM AK (C3-CPU and C4-CPU), you must parameterize
these BSEs and the corresponding PREs in the topology menu.