CLT- & CLX-4HSW4

 

Functional Summary 

The Crestron

 4-Feed, 4-High Switch Terminal Block and 

Module (CLT-4HSW4 and CLX-4HSW4, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-4HSW4 prior to installation of the 
CLX-4HSW4, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate four circuit feeds (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
switching (non-dim) control of four incandescent, low 
voltage, neon, cold cathode, fluorescent, or HID lighting 
loads, or motor loads. The maximum load is 16 amps (1/2 
HP) for each controlled circuit (64 amps total per 
module). The unit requires 120VAC 60 Hz input voltage. 
An oversize heat sink dissipates heat efficiently. There are 
LEDs on the module to indicate communication to a 
Cresnet

 network, input power to the module, and output 

power to the load. 

NOTE:  

When connecting to an Arc Fault Breaker, 

the load should not exceed 1000 watts.  

Industry Compliance 

This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc.  

     

(E103692)

 

Installation 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
32

°

F to 104

°

F (0

°

C to 40

°

C). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 

shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Terminal Block & Module Locations (Single-wide Enclosure) 

MODULE

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

 

 

Terminal Block & Module Locations (Double-wide Enclosure) 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 5986B

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2002068)

 

Tel: 888.CRESTRON

 

08.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

GROUNDING TERMINAL BLOCKS

MODULE

TERMINAL BLOCK

(LEFT)

TERMINAL BLOCK

(RIGHT)

 

Summary of Contents for CLT-4HSW4

Page 1: ...al block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 32 F to 104 F 0 C to 40 C The relative humidity must be 0 to 90 non condensing Terminal blocks are installed along t...

Page 2: ...the modules and terminal blocks along the right side must be inverted when mounting CAUTION Bypass jumpers are provided to allow testing of circuits and to protect the module during installation When properly secured by two screws each jumper on the black and red sections of the terminal block shorts the hot to switch so that the circuit is energized On this terminal block there are four distinct ...

Page 3: ...the terminal to which it should be connected Wires are pre stripped to inch Tighten to 9 in lbs Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the module...

Page 4: ...es following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from ...

Reviews: