Redundancy via CP-6010
112
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
2.5.2.2.2 Return Information Message from SICAM AK to CP-6010
Select the values for the parameters
Lk_Reg
and
Lk_Comp
via the relevant pull-down menu.
The Region and Component should be same as the control message.
Select the parameter
Lk_Cat
as
Redundancy return information
via the relevant pull-down
menu. This represents the status signal of SICAK AK to CP-6010.
Enter the same values for the parameters
CASDU1
and
CASDU2
as provided in the web
parameterization of CP-6010.
Enter the values for the parameters
IOA1
,
IOA2
and
IOA3
for the module as provided in
Configuration for SICAM AK to CP-6010
(start address as provided in the web
parameterization of CP-6010, for instance:
IOA1
=
65
,
IOA2
=
5
,
IOA3
=
0
).
Select the following values via the pull-down menu:
─
Return_inform_function_(RED)
as
redundancy state
─
BSE_(RED)
as
not used
─
PRE_(RED)
as
not used
Afterwards click on
Save
.
Hinweis
For the parameterization of further return information signals, proceed as previously described.
For the configuration of SICAM AK B, proceed according to the same procedure as for SICAM AK A.
The following values must be updated in the SICAM AK B:
•
Region
•
Component
•
CASDU