Redundancy via CP-6010
122
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
2.6.2.3.2 Communication Output Link
After creating the signals, select LNK_1703_SDFR and make necessary changes for
configuring as communication output link.
Select the parameter
Lk_Cat
as
Selective data flow routing
via the relevant pull-down
menu.
Select the parameter
Lk_Prep
as
Activated
via the relevant pull-down menu.
Select the parameter
Selectivity
as
selective
via the relevant pull-down menu.
Select the parameter
PRE
as
PRE1
via the relevant pull-down menu. This value can be
different depending on the used configuration.
Select the parameter
Station_A
as
8
and
Station_B
as
9
via the relevant pull-down menu.
This must be the station number specified in the connection definition of
These signals can be used for priority voting. You can configure different type of errors as
input signal and can assign to priority signals by using CAEx
plus
.