Redundancy via SCA-RS
SICAM RTUs, SICAM AK Redundancy
Unrestricted
59
DC2-026-2.07, Edition 10.2016
•
In the OPM system technique select the node
Address of the redundant BSE's
under
C4:CP-2017/PCCX25
•
Enter the following data (valid for BSE and AU redundancy)
Column name/
Parameter
Description/Value
Comment
Red_sync reg-Nr.
Region number of the other element of the
redundancy pair (BSE); for CPU redundancy
the value 254 is to be entered (own AU)
The mirroring of the
parameter is otherwise not
possible.
Red_sync comp-Nr.
Component number of the other element of the
redundancy pair (BSE)
The mirroring of the
parameter is otherwise not
possible.
Red_sync BSE-Nr.
BSE number of the other element of the
redundancy pair
The mirroring of the
parameter is otherwise not
possible.
•
In the OPM system technique select the node
Synchronization parameter
under C4:CP-
2017/PCCX25: