Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
111
DC2-026-2.07, Edition 10.2016
2.5.2.2.1 Control Message from CP-6010 to SICAM AK
After creating the signals in the Process Technique, select the LNK_1703_SYS and make the
necessary changes for creating the control signal from CP-6010 to SICAM AK.
Select the values for the parameters
Lk_Reg
and
Lk_Comp
via the relevant pull-down menu.
Select the parameter
Lk_Cat
as
Redundancy control message
via the relevant pull-down
menu. This represents the control signal from CP-6010 to SICAM AK A.
Enter the same values for the parameters
CASDU1
and
CASDU2
value as provided in the web
parameterization of CP-6010.
Enter the values for the parameters
IOA1
,
IOA2
and
IOA3
for the module as provided in
Configuration for CP-6010 to SICAM AK
(start address as provided in the web
parameterization of CP-6010:
IOA1
=
1
,
IOA2
=
0
,
IOA3
=
0
).
Select the following values via the pull-down menu:
─
Control_function_(RED)
as
A/P-control
─
BSE_(RED)
as
not used
─
PRE_(RED)
as
not used
─
Priority_(RED)
as
priority 0 (lowest)
Afterwards click on
Save
.
Hinweis
For the parameterization of further control signals, proceed as previously described.
For the configuration of SICAM AK B, proceed according to the same procedure as for SICAM AK A.
The following values must be updated in the SICAM AK B:
•
Region
•
Component
•
CASDU