Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
109
DC2-026-2.07, Edition 10.2016
2.5.2
Example of Global Switchover
2.5.2.1 System-Technical Settings
In both systems SICAM AK, select the menu
Redundancy control
under the M-CPU.
Select the parameter
Redundancy control
as
Global redundancy switchover with
applicational voting
via the relevant pull-down menu. This enables the device to apply the
“global switchover”.
Under
Settings for PREs
, select the PRE on the M-CPU (connected to the voter) as
User
data filter deactivated
via the parameter
Option: User data filter
.
All the other PREs are selected as
System element is being switched to passive
.
Copy all the parameters from SICAM AK A to SICAM AK B and change the IP address of
SICAM AK B.