Redundancy via SCA-RS
26
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
1.2.1.2 SICAM AK - SICAM TM PE, Electrically Connected
Base unit SICAM AK to peripheral elements SICAM TM, electrically connected.
•
To one basic system element
CP-2017/PCCX25 one bus line with max.
16 peripheral elements can be connected
•
The slots for the redundant BSE-pairs are
predefined, in fact: 1+2, 4+5, 7+8, (10+11,
13+14 only in 17 slots mounting rack)
•
Redundant BSEs have to have identical
configuration and identical functionality
•
If peripheral elements are equipped in the
base unit SICAM AK then those can be driven
either by the singular BSE CP-2014 or by the
redundant BSEs CP-2017
•
Depending on the slots of the basic system
elements the socket connectors for the
electrical Ax peripheral bus have to be
selected (for example: slots C4 and C5
socket connectors AXPE-C4 and AXPE-C5)
•
The bus interface modules CM-0843 are
supplied by the power supplies PS-663x.
The power consumption of the CM-0843
(see technical data in data sheet) has to be
considered on the PS-663x
I/O modules (max. 8)
Ax peripheral bus (electrical)
16 Mbps
patch-cable, length up to 3 m
Ax peripheral bus (electrical)
16 Mbps
USB-cable, length up to 3 m
bus interface modules
CM-0843
1 peripheral element
base unit
SICAM AK
peripheral elements
SICAM TM
(max. 16 PE)
ESD
EARTH
FACILITY
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
RY
ER
SICAM
PS-5620
PE-6410
PS-663x
CP-2014
CP-2017
(max. 4)
1
2