Montage
Die Abisolierlänge der Kabelisolation beträgt 21 mm.
Die Kabelisolation darf nicht unterklemmt werden.
Fig. 1
Demontage
Fig. 2
Einspeisebeispiele SMISSLINE 125 A System
Fig. 3–5
Einspeisebeispiele SMISSLINE 250 A
Power Bar System
Fig. 6–8
Montage sur les socles
F
La longueur de dénudage de l’isolant du câble est
de 21 mm. L’isolation du câble ne doit pas être coincée.
Fig. 1
Démontage
Fig. 2
Exemples d’alimentation
SMISSLINE 125 A Système
Fig. 3–5
Exemples d’alimentation
SMISSLINE 250 A Power Bar Système
Fig. 6–8
Assembly
G
The stripping length of the cable insulation is 21 mm.
The insulation must not be trapped into the terminal.
Fig. 1
Disconnection
Fig. 2
Supply variants SMISSLINE 125 A System
Fig. 3–5
Supply variants SMISSLINE 250 A
Power Bar System
Fig. 6–8
Montaggio
I
La lunghezza di spelatura dell’isolamento del cavo
è di 21 mm. L’isolamento non deve essere compresso
nel morsetto.
Fig.1
Smontaggio
Fig.2
Esempi di alimentazione
SMISSLINE 125 A Sistema
Fig. 3–5
Esempi di alimentazione
SMISSLINE 250 A Power Bar Sistema
Fig. 6–8
ABB Switzerland Ltd
Low Voltage Products
Fulachstrasse 150
CH-8200 Schaffhausen
Phone: +41 58 586 41 11
Fax:
+41 58 586 42 22
www.abb.com
ABB Ltd
Tower Court,
Coutaulds Way
Foleshill Enterprise Park,
Conventry
CV6 5NX
United Kingdom
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 200 A IEC
max. 150 A UL
max. 125 A
(IEC/UL)
max. 125 A
(IEC/UL)
max. 200 A (IEC)
max. 200 A (IEC)
max. 400 A
(IEC)
max. 200 A
(IEC)
max. 200 A
(IEC)
> 30°
1
2
4
3
1
4
3
2
1
> 30°
1
2
4
3
1
4
3
2
1
U L d a t a
For all types:
Feeder Blocks cat. nos. ZLS250 – ZLS253, ZLS954UL, ZLS959UL are suitable for use in feeder circuits up to 600 V
Wire required to be fixed 2 inches (50.0 mm) below entry point of component housing by suitable cable ties
Rated Voltage:
600 V AC
Short Circuit Rating:
50 kA, max. 480 VAC and 480 Y/277 V and 240 VAC
Short Circuit Protection:
150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating of 250 A,
located at Line Side
Torque:
2.0 Nm
Stripping length:
21 mm
Wire size:
2 AWG - 1/0 AWG
Wire rated min. 600 V and 75 °C (AVLV2/8)
1
2
max. 125 A (IEC/UL)
max. 125 A (IEC/UL)
max. 200 A
(IEC/UL)
max. 125 A
(IEC/UL)
max. 125 A
(IEC/UL)
max. 200 A (IEC)
max. 200 A (IEC)
max. 200 A (IEC)
max. 200 A (IEC)
max. 200 A (IEC)
max. 200 A (IEC)
max. 400 A
(IEC)
max. 200 A
(IEC)
max. 200 A
(IEC)
4
6
8
3
5
7