Configuration via Web Pages
Configuration of the IEC 61850 Protocol
To change the IEC 61850 settings in the Configuration tab, proceed as follows:
•
In the navigation window, click Communication Ethernet.
•
Select IEC 61850 as the Bus protocol.
[sc_communication_IEC_61850, 1, en_US]
Figure 2-31
Configuration Tab, IEC 61850 Settings
•
Configure the respective parameters according to the following table.
Table 2-20
Settings for IEC 61850
Parameter
Default Setting
Setting Range
IED Name
SICAM_P850/P855_01
Any, max. 60 characters
Only a-z, A-Z, _, 0-9 are permitted.
The first character must be an alpha character.
Voltage - Dead band
5 %
1 % to 5 %, in 1 % steps
Current - Dead band
5 %
1 % to 5 %, in 1 % steps
Power - Dead band
5 %
1 % to 5 %, in 1 % steps
Power factor - Dead band
5 %
2 % to 5 %, in 1 % steps
2.6.3.2
Basic Functions
2.6 Ethernet Communication
70
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...