Indication
Description
Notes
Modbus Serial OK
(Modbus RTU (Slave))
The Modbus serial communication
has received a valid Modbus
message.
Indication ON: At least 1 serial message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No serial message was received during the
set communication supervision time.
IEC 60870-5-103 OK
Communication via protocol IEC
60870-5-103 is correct.
Indication ON: At least 1 serial message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No serial message was received during the
set communication supervision time.
Settings Load
Starting to change the parameters
of the passive set of parameters.
Indication ON: Start of changes
Indication OFF: Changes complete
Settings Check
The passive set of parameters is to
be activated; the internal param-
eter check is running.
Indication ON: Check started
Indication OFF: Check complete
Settings Activate
The passive set of parameters is
enabled and the device works with
these parameters.
Indication ON: Activation started
Indication OFF: Activation complete
Limit Violation x
Indication that a parameterized
limiting value has been violated
Indication ON: The limit of the monitored measured value
has been violated or no measured value is parameterized as
input of the limiting value.
Indication OFF: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is invalid
(for example, frequency at V < 15 % of V
rated
).
x = 1 to 16
Indication 1 from
Remote
Status of the indications that can
be set to control the LEDs and the
binary outputs via the communica-
tion.
Indication ON: ON
Indication OFF: OFF
Message invalid: Not yet updated via the communication or
again invalid via the communication
Indication 2 from
Remote
Reset Energy
The energy counters were reset.
Indication ON: Energy counters reset
Rotating Field Clock-
wise
Indication of rotation voltage
Indication ON: Phase sequence Va-Vb-Vc, rotation clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases inter-
changed); rotation counter-clockwise
Indication invalid: Direction of rotation cannot be calcu-
lated (for example, no voltage applied)
Group indication x
Up to 4 single-point indications can
be linked logically and combined to
a group indication.
A total of 4 group indications can be parameterized.
x = 1 to 4
Voltage Event Avail-
able
Indication of a voltage event
Voltage dip, voltage swell, and voltage interruption
Voltage Dip Start
Start of a voltage dip
Voltage dip
Voltage Swell Start
Start of a voltage swell
Voltage swell
Voltage Interruption
Start
Start of a voltage interruption
Voltage interruption
Voltage Unbalance
Event Available
Indication of a voltage unbalance
event
Voltage unbalance
Frequency Event Avail-
able
Indication of a frequency event
Overfrequency or underfrequency
Operational Indications and Operating Parameters
13.1 Operational Indications
SICAM, SICAM P850/P855 7KG85X, Manual
261
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...