To insert the battery, observe the notes in the supplied Product Information and proceed as follows:
•
Pull out the battery compartment.
•
Take the battery out of the battery compartment.
•
Remove the plastic foil.
•
Insert the battery into the battery compartment.
•
Push the battery compartment back in again.
Replacing a Used Battery
!
WARNING
Warning of incorrect treatment of the lithium battery (type PANASONIC CR2032 or VARTA 6032 101 501)
or the use of an incorrect battery type. In the case of incorrect treatment or the wrong battery type, the
battery may burn, explode or trigger a chemical reaction.
See product information for type of battery to be used.
Non-observance may lead to death or serious injury.
²
Installing the battery or replacing it may only be carried out by trained personnel (see Preface) who
are familiar with and observe the safety requirements and precautions.
²
Do not reverse the polarity of the battery.
²
Do not short-circuit the contacts. Use non-conducting tools for removing and installing the battery.
²
Do not attempt to open the battery.
²
The battery used in this device may present a fire or chemical burn hazard if mistreated. Do not
recharge, disassemble, heat above 100 °C (212 °F) or incinerate.
²
Dispose of used battery promptly. Keep away from children.
Replace the batteries if the battery charge is too low (avoid full discharge). In this case, the Battery Failure
operation indication is generated. This message can also be parameterized on one of the LEDs H1 to H2/ERROR
or switched to one of the binary outputs (see chapter
3.2.2 Configuration and Value View via Web Pages
).
When the Battery Failure indication is displayed, replace the battery as follows:
•
Pull out the battery compartment.
•
Remove the new battery type PANASONIC CR2032 or VARTA 6032 101 501 from the packaging (check
the expiry date on the packaging).
•
Insert the battery carefully into the battery compartment with the polarity indicated above the battery
compartment.
•
Push the battery compartment back again.
i
i
NOTE
The internal battery test in the device is executed once within 24 hours as well as at the startup of the
device. After replacing an empty battery the indication Battery Failure is reset only with the next regular
internal battery test.
Commissioning and First Steps
9.2 Unpacking, Inspecting the Delivery, Installing, and Changing the Battery
190
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...