Air humidity data
Mean relative humidity per year
≤ 75 %
Maximum relative humidity
95 % 30 days a year
Condensation during operation
Not permitted
Condensation during transport and
storage
Permitted
Altitude and operation site
Max. altitude above sea level
2000 m
Operating site
Indoors use
Climatic Stress Tests
Standards: IEC 60068
Dry cold:
IEC 60068-2-1 test Ad
Dry heat during operation, storage, and transport:
IEC 60068-2-2 test Bd
Damp heat:
IEC 60068-2-78 test Ca
Change of temperature:
IEC 60068-2-14 test Na and Nb
General Data
Battery
Type
PANASONIC CR2032 or
VARTA 6032 101 501
Voltage
3 V
Capacity
230 mAh
Typical life
For operation with permanently
applied supply voltage:
10 years
For operation with sporadically
interrupted supply voltage:
A total of 2 months over a 10-year
period
Internal memory
Capacity
2 GB
Degree of protection
DIN rail housing
IP20
Panel flush mounting (front)
IP40 (with display, without door)
IP51 (with display and door)
Terminals
IP2x
12.1.5
Technical Data
12.1 Technical Data
SICAM, SICAM P850/P855 7KG85X, Manual
249
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...