Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
87
Operating times of the 3VL
Unit
2x
3VL 160X
+ 2x MO
2x
3VL 160X
+ 2x SEO
2x
3VL 160
+ 2x MO
2x
3VL 160
+ 2x SEO
2x
3VL 250
+ 2x MO
2x
3VL 250
+ 2x SEO
2x
3VL 400
+ 2x MO
Contact trans-
fer time, off-
time*
ms
1100
200
1100
200
1100
200
1100
Time II-O, I-O
ms
1000
5000
1000
5000
1000
5000
1000
Time I-O-II (for
min parame-
ter)*
ms
2100
5200
2100
5200
2100
5200
2100
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Unit
2x
3VL 400
+ 2x SEO
2x
3VL 630
+ 2x MO
2x
3VL 630
+ 2x SEO
2x
3VL 800
+ 2x MO
2x
3VL 800
+ 2x SEO
2x
3VL 1250
+ 2x MO
2x
3VL 1600
+ 2x MO
Contact transfer time,
off-time*
ms
300
1100
350
1100
350
5100
5100
Time II-O, I-O
ms
5000
1000
5000
1000
5000
5000
5000
Time I-O-II (for min
parameter)*
ms
5300
2100
5350
2100
5350
10100
10100
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Operating times of the 3WL
Unit
2 x 3WL11
2 x 3WL12
2 x 3WL13
Contact transfer time,
off-time*
ms
180
200
200
Time I-O, time II-O
ms
73
73
73
Time I-O-II (for min
parameter)*
ms
253
273
273
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position