
Operation
8.1 Operating modes of the ATC6300
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
103
If the closing of one switching device is manually controlled, and provided the other is still
closed, the mechanism first opens the other switching device and then closes the controlled
switching device after the programmed delay time.
Note
Releasing locked pages
As long as the opening/closing of the switching devices is enabled, scrolling through the
pages is locked. By repeatedly pressing the MAN key, it can be released in order to open
other pages.
In the case of a network/generator or generator/generator application:
If gen-sets are used, these must first be started manually before they can be connected.
1.
Select the MAN operating mode.
On selection of the mode, the following window opens:
2.
Press the
▼ key.
This opens the window for manually starting the generator.