Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
99
General setting
Table: Output function
Table: Input function
Param-
eter
Setting Con-
nection
Param-
eter
Setting
Con-
nection
Param-
eter
Setting
P05.07 Chg.
Pul.
25
P11.04.
01
Open Line 1 circuit
breaker
15
P10.01.
01
Line 1 breaker closed (feedback 1)
27
P11.05.
01
Close Line 1 circuit
breaker
16
P10.02.
01
Line 2 breaker closed (feedback 2)
28
P11.06.
01
Open Line 2 circuit
breaker
17
P10.03.
01
Line 1 circuit breaker protection (Trip
1)
30
P11.07.
01
Close Line 2 circuit
breaker
18
P10.04.
01
Line 2 circuit breaker protection (Trip
1)
7.3.8
Connection of the 3KC3 / 3KC4 transfer switching equipment
Note
According to IEC regulations, the fusible element must be connected via a cable compliant
with IEC 61439-1 which is protected against ground faults and short circuits. To this end,
please observe the applicable national standards for electrical installations.