Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
143
9.3.15
P15 - User alarms
This menu is divided into 4 sections for the definition of the user alarms UA1 ... UA4.
You can find more information in chapter User alarms (Page 50).
P15 User
alarms
(UAn,
n=1…4)
Designation on
ATC display
Description
Default Range
P15.n.01
Source
Alarm source
– Defines the digital input or of the internal variable that
generates the user alarm when it is activated.
OFF
OFF
INPx
OUTx
LIMx
REMx
P15.n.02
Channel number Channel number (x)
– Channel number, with reference to the previous parame-
ter
1
OFF / 1 ... 99
P15.n.03
Description
Description
– Freely selectable text that is shown in the alarm window.
UAn
(Text – 20
chars)
P15.n.04
Breaker opening Opening of the circuit breaker
– It is defined which breaker is to be opened when this
alarm occurs.
Example: The user alarm UA3 must be generated by the
closing of input INP5 and must display the message
"Doors open".
In this case, the menu section 3 must be configured (for
alarm UA3):
P15.3.01 = INPx
P15.3.02 = 5
P15.3.03 = ‘Doors open’
OFF
OFF
1
2
1+2