Functions
5.1 Basic functions
3KC ATC6300 transfer control device
50
Manual, 03/2018, L1V30535632002A-01
To activate or deactivate the property of an alarm, the option must be selected or deselected
for the corresponding alarm:
①
Alarm 01 Enabled property activated
②
Alarm 01 Enabled property deactivated
●
Press the ▲ or ▼ keys to jump from one alarm to the next (A01, A02, etc.)
●
The + / MAN key is for switching between the properties
●
The - / RESET key is used for closing the alarm table
●
Properties can be selected/deselected with the ✓ key
5.1.6.4
User alarms
The user can define up to four programmable alarms (UA1…UA4). For each alarm, the
following can be specified:
●
The source, i.e. the condition that triggers the alarm.
The following functions can be used as alarm sources:
–
LIMx: The alarm is triggered if a user limit is exceeded
–
INPx: An alarm can be triggered by a signal via an input
–
OUTx: An alarm can also be triggered by the activation of an output
–
REMx: Using a remote variable, an alarm can be activated/deactivated via Modbus
●
or text of the message that must appear on the display when this condition occurs (see
example in chapter P15 - User alarms (Page 143)).
●
the properties of the alarm (see chapter on Alarms (Page 46))
If several alarms occur simultaneously, they are displayed sequentially, with an indication of
the total number of alarms.
By pressing the OFF-RESET key, retained alarms can be canceled, provided the causes of
the alarms have been eliminated.
An alarm programmed with a memory is reset using the corresponding command in the
command menu.
For the definition of the alarms, please refer to the setup menu P15 - User alarms
(Page 143)