Functions
5.1 Basic functions
3KC ATC6300 transfer control device
42
Manual, 03/2018, L1V30535632002A-01
5.1.4.1
Enabling additional resources
The expansion modules provide additional resources that can be used via the corresponding
setup menus.
Note
Availability during physical absence of modules
The setup menus for the expansions are also available if the modules are not physically
present, i.e. the inputs 6-14 on the device can be parameterized, even though no module is
inserted and these inputs are therefore not available.
As it is possible to add several modules of the same type (for example, two communication
interfaces), several of the corresponding setup menus are available and are identified by
consecutive numbering.
The table below shows how many modules of each type can be installed simultaneously and
in which slots they may be used. There must be no more than two modules.
Module type
Article number Function
Maximum num-
ber that can be
inserted
Communica-
tion
3KC9000-
8TL74
RS485 (MODBUS RTU)
2
3KC9000-
8TL75
Ethernet (MODBUS TCP)
1
Digital inputs
and outputs
3KC9000-
8TL60
4 digital inputs
2
3KC9000-
8TL61
4 digital outputs, SSR (4 NO contacts)
2
3KC9000-
8TL62
2 digital inputs and 2 digital outputs, SSR (2 NO
contacts)
2
3KC9000-
8TL63
2 digital relay outputs (2 changeover contacts)
2
3KC9000-
8TL64
2 digital inputs and 2 relay outputs (2 NO con-
tacts)
2