Operation
8.1 Operating modes of the ATC6300
3KC ATC6300 transfer control device
104
Manual, 03/2018, L1V30535632002A-01
3.
Using the MAN key, select the line that you want to close (in this case the generator is
located on Line 2).
4.
Press the
▲ and ▼ keys to start or stop the selected generator.
5.
After starting the generator, press the MAN key again to return to the manual control
(item 2).
The generator has now been started.
6.
Press the ▲ key to switch back to the manual activation of the switching devices.
7.
Press the MAN key in order to select the switching device of Line 2 (see procedure for
network/network application).
The selected line is opened and closed by pressing
▲ and ▼.
If the closing of one switching device is manually controlled, and provided the other is still
closed, the mechanism first opens the other switching device and then closes the controlled
switching device after the programmed delay time.
If generators are being used, the generator continues running in the cooling mode after
stopping.