Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
124
Manual, 03/2018, L1V30535632002A-01
9.3.4
P04 - Battery
Note
Use of DC power supply
The following parameters are necessary only if you are using a DC power supply (see
chapter Connecting the power supply (Page 70)).
P04
Battery
Designation on ATC
display
Description
Unit
Default
Range
P04.01
Battery voltage
Nominal voltage of the DC supply
– This parameter defines the voltage of the
additional DC supply of the ATC6300.
Note: If this parameter is set to OFF, all alarms
regarding the DC supply, as well as the indica-
tor for the battery voltage, are disabled.
V
AUTO
AUTO
12
24
OFF
P04.02
Max voltage limit
Maximum voltage limit of the DC supply
– This defines the upper limit threshold for the
battery voltage.
%
130
110 - 140
P04.03
Min voltage limit
Minimum voltage limit of the DC supply
– This defines the lower limit threshold for the
battery voltage.
%
75
60 - 130
P04.04
Min / Max volt. delay Minimum / maximum voltage delay of the DC
supply
– This parameter defines the delay for the min-
imum / maximum DC supply voltage. If the
voltage exceeds the upper or lower limits from
P04.02 and P04.03 for the period defined by
this parameter, the corresponding alarms are
triggered.
s
10
0 - 120