Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
76
Manual, 03/2018, L1V30535632002A-01
Generator/generator transfer
The output Control Generator 2 must then be programmed in such a way that the generator
is started when the ATC6300 is de-energized.
Connection
Parameter
Output type
Setting
OUT (3) 22 - 23
P11.03.01
NOR
Control Generator 2
OUT (2) 11 - 12
P11.02.01
REV
Control Generator 1
7.3
Connection of Siemens SENTRON switching devices
The connection of the Siemens switching devices is shown below
7.3.1
Accessories for switching devices
The following accessories are necessary for the Siemens switching devices:
Circuit breaker
Accessories required
3KC
Emergency pushbutton
3VA
Auxiliary switch (interlock)
Auxiliary switch (status)
Alarm auxiliary switch (trip)
Motor operator
3VL
Auxiliary switch, normally open (NO) (interlock)
Auxiliary switch, normally closed (NC) (status)
Alarm auxiliary switch (trip)
Motor operator
3WL
Auxiliary switch (interlock)
Auxiliary switch (status)
Tripped signaling switch (trip)
Auxiliary trip unit (shunt release) F1
Closing solenoid Y1
Motor operator
3WT
Auxiliary switch (interlock)
Auxiliary switch (status)
Tripped signaling switch (trip)
Auxiliary trip unit (shunt release) F1
Closing solenoid Y1
Motor operator