Technical specifications
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
197
Relay outputs OUT4 and OUT5, as well as OUT6 and OUT7: Terminals 25, 26, 27 and terminals 28,
29, 30
Contact type
4x1 NO contacts (OUT4 and OUT5 as well as
OUT6-7 with common control terminal)
Rated contact current
AC1 8 A 250 V
DC1 8A 30 V
AC15 1.5 A 250 V
UL Rating
B300
30 V DC 1A pilot duty
Output voltage (maximum)
250 V AC
Mechanical / electrical endurance
1x10^7 / 1x10^5
Insulation voltage U
i
250 V AC
Design of insulation
Single between OUT4-5 and between OUT6-7
Double for the remaining groups
Single / double
Impulse withstand voltage U
imp
4.8 kV / 7.3 kV
Operating frequency impulse withstand volt-
age
1.5 / 3 kV
Ambient conditions
Operating temperature
-30 … +70 °C
Storage temperature
-30 … +80 °C
Relative humidity
< 80 % (IEC / EN 60068-2-70)
Maximum degree of pollution
2
Overvoltage category
3
Measuring category
CAT III
Connections
Connecting terminals
Removable / plug-in
Cable cross-section (min-max)
0.2 … 2.5 mm
2
(AWG 24 ... 12)
Cable cross-section (min-max) acc. to UL 508 0.75 … 2.5 mm
2
(AWG 18 ... 12)
Tightening torque
0.56 Nm (5 lbf-in)
Enclosure
Enclosure material
Polyamide
Version
Door installation
Degree of protection
IP40 at front (can be increased to IP65 by using
cover frame), IP20 at rear
Weight
600 g