Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
133
P07 Pa-
rameter
Line 2
Designation on ATC
display
Description
Unit
Default Range
P07.09
Phase failure thresh Threshold limit for phase failure
%
70
60 – 80
OFF
P07.10
Phase failure delay Delay time for the phase failure threshold limit
s
0.1
0.1 s - 30 s
P07.11
Max. asymmetry
limit
Maximum limit for asymmetry of the phases
%
15
1 % -
20 % / OFF
P07.12
Max asymmetry
delay
Delay time for maximum asymmetry of the
phases
s
5
0.1 - 900
P07.13
Max frequency limit Limit for the maximum frequency
%
105
100 -
120 / OFF
P07.14
Max frequency
delay
Delay time for the maximum frequency
s
3
0 - 600
P07.15
Min frequency limit Limit for minimum frequency
%
95
OFF / 80 - 100
P07.16
Min frequency delay Delay time for minimum frequency
s
5
0 - 600
P07.17
Line cont. OFF
mode
Setting of the voltage measurement in the OFF
mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.18
Line cont. MAN
mode
Line 2 control in MAN mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.19
Generator start
delay
Delay of generator start after failure of Line 2
s
OFF
OFF / 1 - 6000
P07.20
Cooling time
Generator cooling time
s
120