Parameterization
9.1 Parameterization via the user interface
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
117
If access is possible, the following window appears:
①
New value entered
②
Maximum possible setting
③
Factory default setting
④
Minimum possible setting
⑤
Parameter code
⑥
Parameter description
This window contains information on the range of values, the minimum and maximum
values, the previous setting, and the factory default setting.
9.1.1
Changing the parameters
●
The parameters can be changed using the + and – keys.
●
Pressing the + and – keys simultaneously leads to the factory setting.
●
For a text string entry, the character is selected using the ▲ and ▼ ke
ys and the cursor is
moved through the text using the + and – keys.
●
By pressing ▲ and ▼ simultaneously in the case of a text entry, the character selection is
set to the letter A.
●
By pressing the ✓ key, the currently selected parameter is stored.
The device then returns to the menu one level above this (in this case, to the P04 Battery
diagram).
●
You can exit the setup menu by pressing OFF.
Note
Restart after parameter change
After each parameter change the device executes a restart. If it remains in the setup menu
for more than two minutes without any changes being made, the device will also restart.
After the restart, the ATC is in the OFF mode.