Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Large plants
30.08.2007
KNX network linked via IP router to IP network (area line 0)
1.2.1
1.1.1
RM...
1.1.2
RM...
1.1.250
RM...
1.2.2
RM...
1.2.250
RM...
RM...
1.15.1
RM...
1.15.2
RM...
1.15.250
RM...
N140/13
1)
1)
N140/13
1)
N140/13
N146
1)
1.0.1
RM...
RM...
1.0.2
1.0.250
2)
N146
1)
N146
15.0.10
RX...
15.0.250
1)
N140/13
USB
2.0.254
IP 192.168.10.1/24
RM...
IP 192.168.10.1/24
15.0.1
RM...
RMB...
15.0.2
RX...
IP 192.168.10.15/24
2.0.150
OZW775
RMZ792
2.0.252
15.1.10
RX..
15.1.250
RMB...
15.1.1
RX...
Li
n
e
1
Li
n
e
2
Li
n
e
15
Main line 1
Ma
in
l
in
e
2
Li
n
e
1
Main line 15
31
2
7
Z
4
3e
n
IP network (Area line 0)
PC with ACS
Service
interface
Service
cable
Ac 1.0.0
Ac 2.0.0
Ac 15.0.0
Lc 1.1.0
Lc 1.2.0
Lc 1.15.0
Lc 15.1.0
LTE filter table: 1) Normal (route), 2) Route all
If Synco devices are used as alarm drains (see OZW775 central communication
unit and RMZ792 bus operator unit in the illustration), these alarm drains must be
installed directly after an IP router.
To enable the alarm drains to receive all alarm signals (and other data) from the IP
network, the IP router filter must be set to "Forward all" (see section 8.2.1 and
8.2.5).
Example 2
Alarm drains
Alarm signals