34/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device addresses via ACS
30.08.2007
The following Synco devices have a tool interface and can be connected directly to
a PC/laptop via the OCI700 service interface:
•
RM… controllers
•
RX… room controllers
•
QAX910 central apartment unit
The QAW740 room unit and OZW77x central communication units do not have a
tool interface. Communication with these devices is possible indirectly, via Synco
devices with a tool interface and the KNX bus.
5.1.2 New
plant
If it does not already exist, a new plant must be set up. With a connection via the
OCI700 service interface,
OCI700 - KNX
must be selected as the type of central unit.
Select, Type of central unit
OCI700 - KNX
Complete the input by clicking
Finish
Description of the information in the "Communication" dialog box under "Konnex
bus system" (see screenshot on the right)
•
Device at OCI700
Only the device connected to the OCI700 service interface is imported into the
device list. If the OCI700 service interface is connected to a bus socket, no
devices are recognized.
•
Line at OCI700
All devices belonging to the same line as the device that is connected to the
OCI700 service interface are included in the device list. Line couplers are not
included in the list.
•
All lines
All devices in the KNX network, including area/line couplers and Siemens IP
routers (see section 1.4) are included in the device list.
Synco devices with
a tool interface
Note
Central unit type
Notes on the Konnex
bus system