Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device address and device name
30.08.2007
4.2
Setting device address with RMZ790 and
RMZ791 operator units
Synco bus devices with factory-set device address 255 do not transmit process
values. However, these devices can be operated, and the device address can be
set. The address range is 1…253 excluding 150, which is reserved for the
OZW775 central communication unit.
Access to the basic communication settings is via the Password Level (symbol ).
The device address is then set via the "Basic settings" page on the "Device
address" line. The procedure is as follows:
Main menu > Commissioning > Communication > Basic settings
Turn the knob as required for access to setting mode.
In setting mode, set e.g. Device address=10 by rotating the knob as required.
Press the knob to confirm the setting. An internal test to check for address conflicts
is indicated by the hourglass symbol.
When there are no more basic settings to be modified, the commissioning process
must be terminated (see section 3.2.2).
Device addresses can also be assigned to a device via ACS (see section 5).
Introduction
Setting procedure
Step 1
Step 2
Step 3
Step 4
Note
Basic settings
Device address: 10
Dec bus power supp: On
Clock time op: Master
Rem set clock slave: Yes
Device address
255
1
255
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Device address
10
1
255
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Basic settings
Device address: 255
Dec bus power supp: On
Clock time op: Master
Rem set clock slave: Yes