Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device addresses via ACS
30.08.2007
5.2.4
Addressing via the ID number
If the devices to be addressed are a long way from the PC/laptop running ACS
Service (e.g. devices in the basement, PC/laptop on KNX bus in control panel on
first floor) then addressing via individual ID numbers is recommended.
1.
Read the IDs
locally
from the devices to be addressed
12-digit hexadecimal number, e.g. ID:
00FD0000139D
2. In ACS Service select
Plant > Edit device list…
to open
the "Edit device list" dialog box.
3. Identify the device from its ID and select it.
4. Assign an address manually (see section 5.2.1)
5. Identify the next device from its ID, select it and carry out Step 4 etc.
For all the programming modes described for the RM… controllers, the area and
line addresses are automatically adopted by the area/line couplers and IP routers.
If there are no couplers or routers, the factory-set area/line address 0.2 is used.
Procedure
Important notes