99/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Appendix
30.08.2007
Main menu > Commissioning > Extra configuration > Heating/cooling changeover
Operating line
Range
Factory setting
Heating/cooling based on calendar
No, Yes
No
Main menu > Commissioning > Settings > Heating/cooling changeover
Operating line
Range
Factory setting
Start date, heating
01.01. - 31.12.
01.10.
Start date, cooling
01.01. - 31.12.
01.05.
The changeover occurs on the "Start date, heating" or "Start date, cooling".
9.2.4
H/C changeover relay and fault messages
If, instead of being transmitted over the bus, the H/C changeover signal is to be
made available at a relay output e.g. for switch control of a valve or for forwarding
to a non-communicating device, the H/C changeover relay can be configured
accordingly. See the notes on connecting the primary controller to the changeover
valve.
Main menu > Commissioning > Extra configuration > Heating/cooling changeover
Operating line
Range
Factory setting
Heating/cooling changeover relay
----, N.Q1, N.Q2,…/
----
The current contact position (status) of the changeover relay can be displayed via
the Service level.
Main menu > Heating/cooling changeover
Operating line
Current contact position (status)
Heating/cooling changeover relay
Open (Off) Cooling / Closed (On) Heating
In a 2-pipe heating/cooling system without a "Heating/Cooling changeover" signal
on the KNX bus, the controller continues to use the last received value. If the signal
never existed, then "Heating" is used as the default value.
No.
Text
Effect
5801 H/C
changeover
signal failure
Non-urgent message; no acknowledgement
required.
If the "H/C changeover" in a 2-pipe system is configured so that it is initiated by
calendar or by operating mode selector, and a changeover signal is received in one
of the zones from another device, then the fault message "> 1 heat/cool
changeover signal" is transmitted.
No.
Text
Effect
5802 >1
heat/cool
changeover signal
Non-urgent message; acknowledgement is
required.
Configuration
Settings
Heating/cooling
changeover relay
Configuration
Current contact position
Fault status messages
H/C changeover signal
failure
Fault status message
5801
> 1 H/C changeover signal
Fault status message
5802