67/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Communication via zone addresses
30.08.2007
7
Communication via zone addresses
7.1
General notes on zones
7.1.1 Synco
zoning
Zoning in Synco is based on KNX and covers the following zones for Synco 700
devices and RXB/RXL room controllers:
Designation
RMU
RMH
RMK
RMB
RMS
QA
W
RXB
RXL
Zone
address
range
Def'
value
RM...
Def.
value
RX…
Geographical zone (apartm)
x x x x x x x x 1…126 ----
/1
----
Geographical zone (room)
x x x x x 1…63
* ----
/1
1
Geographical zone (subzone)
x x 1…15
*
1
Time switch zone (apartment)
x x 1…126
1
Time switch zone (room)
x x 1…63
*
1
Time switch zone (subzone)
x x 1…15
*
1
Time switch slave (apartment)
x x x x 1…126 ----
/1
Master/slave zone (apartment)
x x 1…126
1
Master/slave zone (room).
x x 1…63
*
----
Master/slave zone (subzone)
x x 1…15
*
1
QAW op.zone (apartment)
x 1…126 ----
Heat distribution zone
x x x 1…31
1
Heat distr zone source side
x x x x 1…31
----
Heat distr zone consumer side
x
x x 1…31 1
/
2
Heat distr zone heating surface
x x 1…31
----
Heat distribution zone air heater
x x 1…31
----
Heat distrib. zone, primary distr.
x
1…31 1
Heat distrib. zone, primary contr.
x 1…31
2
Refrigeration distribution zone
x x 1…31
1
Refrig distr zone source side
x x x 1…31
----
Refrig distr zone consumer side
x x 1…31 ----
/1
Refrig distr zone cooling surface
x x 1…31
----
Refrig distrib. zone cooling coil
x x 1…31
----
Air distribution zone
x 1…31
1
Boiler sequencing zone
x 1…16
1
DHW zone
x 1…31
1
Holiday/special day zone
x x x x x 1…31
----
/1
Time switch, DHW slave
x 1…31
1
Outside temperature zone
x x x x x x x 1...31
----
/1
1
Solar zone
x 1...31
----
Wind zone
x 1...31
----
---- / 1 Depending on the device, the default is "----" (e.g. RMU7x0B) or "1" (e.g. RMU7x0).
See also section 7.1.4 for information on the default "----" with the series B devices.
----
With RXB/RXL room controllers "----" indicates that the zone is "out of service" and there are no
process values transmitted from this zone (in the QAX34.3 room device, "-1" is displayed
instead of "----".
*
The zone address range for the RXB/RXL room controllers is 0…63 or 0…15.
Zones and devices