73/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Communication via zone addresses
30.08.2007
Press the knob to confirm the zone address just set.
Geographical zone (apartment), RM… controllers
RM… default
1
RM… B default
----
Settings
1...126
In extensive networks it is more efficient to set zone addresses via ACS Service
than to use the RMZ790 and RMZ791 operator units (see section 5.1).
7.2.2
QAWZ740 room unit
The QAW740 room unit only contains the "Geographical zone (apartment)". The
zone address can be set by use of the operator controls on the front of the unit.
Step
Action
Operator
controls
1
For access to the setting mode, press the presence
button for approximately 6 seconds. A letter
A
is
displayed and the zone address can be set.
2
Set the zone address with the rotary knob,
In this example, the value is 5, hence
A 5
Note:
A
stands for "Geographical zone (
A
partment)"
3
Briefly pressing the presence button again takes the
user to other settings (for setting values with rotary
knob, see Step 2).
4
After setting the zone address, press the presence
button to exit from setting mode.
Zone address in the range 1…126 can be set for the "Geographical zone
(apartment)" in the QAW740 room unit.
Step 4
RM…controllers
RM…B controllers
Zone addresses
in
networks
Setting procedure
Note
Room
Geogr. zone (ap.): 5
Time switch op: Autonom
TS slave (apart.): 1
Room
Geogr. zone (ap.): 5
TS slave (apart.): ----
Time switch op: Autonom