46/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device addresses via ACS
30.08.2007
The device address can be set manually via "Device address" line on the "Basic
settings" operating page. The path for this setting is:
Main menu > Commissioning > Bus communication
Commissioning
Basic configuration…
RF connections…
Device list…
Bus communication…
Basic settings
Basic setings
Device address 255
Bus power supply Off
Programming mode Off
Device address
Device address
255
100
1
Select the "Device address" line and enter a device address in the range 1…253
(excluding 150).
When the input is complete, the central apartment unit checks whether this address
is already in use. If it is not in use, the display reverts to the "Basic settings" page.
This means that the address entered is permissible and has been adopted.
If a device address is entered which is already in use, the address is not adopted.
The display does not revert to the "Basic settings" page.
The device address can be determined in programming mode via the
"Programming mode" line on the "Basic settings" operating page. For access, the
central apartment unit must be set
locally
to "Programming mode = On" via the
following path:
Main menu > Commissioning > Bus communication > Basic settings > Programming mode
Basic settings
Device address 255
Bus power supply Off
Programming mode On
Operating pages
(display)
Procedure
Note
Programming mode