88/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Large plants
30.08.2007
The recommendation on the previous page is particularly important in relation to a
network with a large number of RX… room controllers.
In a line containing up to 62 RX… room controllers, an RMB795 central control unit
is used as a "collector". The area/line couplers are set to "Normal (route)".
The heating and refrigeration distribution zone in each RX… room controller is con-
figured with a zone address in the range
1...15 (data communication within the line).
The heating and refrigeration distribution zone in each RX… room controller is
configured on the consumer side with a zone address in the range
16...13 (data
communication via area/line coupler).
The heating/refrigeration demand from the RX… room controllers is transmitted by
the "collector" to the RMH primary heating and RMU primary cooling controllers.
N140/13
1)
N140/13
1)
RMU
RMH
1.0.1
1.0.2
0.2.150
OZW775
1)
N140/13
0.2.254
3)
N140/13
2)
N140/13
0.2.252
RMZ792
RX...
15.1.2
15.1.1
RX...
2.0.20
RX...
2.0.21
RX...
RX...
1.1.64
RX...
1.1.2
RMB...
1.1.1
N140/13
1)
RX...
1.15.64
RX...
1.15.2
RMB...
1.15.1
RM...
15.0.3
RM...
15.0.4
RM...
2.0.2
RM...
15.0.1
RM...
15.0.2
RM...
2.0.1
15.1.3
RX...
15.1.4
RX...
62 RX...
4 RX...
2 RX...
62 RX...
AC 120...230 V
+
-
~
N125/x1
USB
Li
ne
1
Heat zone source
Refrig zone source
Heat zone consumer 1
Refrig zone consumer 1
Li
ne
15
Main line 1
Li
ne
1
Main line 15
Bus power supply
Area 0
ACS alarm
pager, SMS, fax
PC with ACS
Service-
Interface
RJ45
connector
Bus connector
socket
Sercice cable
Ac 1.0.0
Ac 2.0.0
Ac 15.0.0
31
27
Z4
5e
n
Heat distr zone 16
Refrig distr zone 16
Heat distr zone 16
Refrig distr zone 16
Lc 1.1.0
Lc 15.1.0
Lc 1.15.0
Heat distr zone 16
Refrig distr zone 16
16
16
Heat zone source
Refrig zone source
16
16
Heat zone consumer 1
Refrig zone consumer 1
Heat distr zone
Refrig distr zone
1
1
Heat distr zone
Refrig distr zone
1
1
Heat distr zone
Refrig distr zone
1
1
Heat distr zone
Refrig distr zone
1
1
Heat distr zone
Refrig distr zone
1
1
Heat distr zone
Refrig distr zone
1
1
Mai
n
l
ine
2
LTE filter table: 1) Normal (route), 2) Route all, 3) Block all
Network with
RX… room
controllers