SV800/SV800A User Manual 6 Function Parameters List
91
<2>: The carrier frequency initialization data and range change according to the inverter module. Here the
carrier frequency range only the inverter can operates. If the carrier frequency is higher than the default
value, the inverter should be derating used.
<3>: When A0-06 = 1, A1-00 and the mapped A1-01 ~ A1-49 set values will be restored to the factory default.
When A0-06 = 2, the A1-00 set value remains unchanged, but the mapped A1- A1-49 set values will be
restored to the factory default. At the same time, pay attention to the backup of the parameters b1-00 ~
b1-16 of the motor parameters group that has been obtained by full-mode self-learning when under vector
control.
A1: Customer application parameters
No.
Name
Content
Set value
A1-00
(0100H)
Application selection
ALL
0: User defined
1: General speed regulation
2: Air supply / exhaust fan
3: Constant pressure water supply (one inverter one pump, one
inverter two pumps)
4~20: Reserved
Factory default: 1
Range:0~ 20
<1>
A1-01
(0101H)
Varies by application
selection
<2>
A1-02
(0102H)
Varies by application
selection
A1-03
(0103H)
Varies by application
selection
...
Varies by application
selection
A1-49
(0131H)
Varies by application
selection
<1>: Group A1 parameters is convenient for user to set SV800 series inverter parameters. When the
application has been selected in A1-00, the A1-01-A1-49 can automatically map a variety of function
parameters and arrange them according to the application. The function parameters not need to be set can
keep it as factory default and the unmapped parameters can also be set in the general function code group.
For detailed mapping parameters of A1-01 ~ A1-49, please refer to Appendix D.
<2>: Initial values of A1-01-A1-49 parameters, Minimum and Maximum value vary with mapping
parameters.