SV800/SV800A User Manual 7 Detailed function description
139
No.
Name
Set range
Factory default
A0-12
G/P model selection
0
~
1
0
0: G type
Generally drive load with constant torque or heavy load
1: P type
Generally drive light load like centrifugal fan or pump etc.
When select P type, the monitoring value U5-00 inverter power will change automatically and
the carrier frequency A0-05 is automatically changed to 2KHz. In general, please do not
increase the carrier frequency. Control mode A0-04 is generally set to V/F control, but vector
control also supported.
No.
Name
Set range
Factory default
A0-13
Speed command unit selection
0
~
2
1
0: 0.1 Hz
The unit dimension of the relevant speed command is Hz, the Min. resolution is 0.1 and the
Max. of E0-02 is 400.0 Hz.
1:0.01Hz
The unit dimension of the relevant speed command is Hz, the Min. resolution is 0.01 and the
Max. of E0-02 is 199.99 Hz.
2:1r/min
The unit dimension of the relevant speed command is r/min, the Min. resolution is 0.1 and the
Max. of E0-02 is 14700r/min.
7.1.2 A1:Customer application parameters
A1 group parameters are mainly used to set customer application parameters, which is
convenient for viewing and modifying common parameters of the application site.
No.
Name
Set range
Factory default
A1-00
Application selection
0
~
20
1
A1-01
~
A1
-
49
Varies by application selection
Varies by application Varies by application
Group A1 parameters is convenient for user to set SV800 series inverter parameters. When the
application has been selected in A1-00, the A1-01-A1-49 can automatically map a variety of
function parameters and arrange them according to the application. The function parameters not
need to be set can keep it as factory default and the unmapped parameters can also be set in the
general function code group.
0: User defined
By setting A0-02=3, the user can define the mapping function parameters of A1-01~A1-49.
1: General speed regulation
The user setting is for general speed control, and A1-01~A1-49 automatically correspond to the
function parameters mapped by the manufacturer. For details, please refer to Appendix D.