6 Function Parameters List SV800/SV800A User Manual
128
P0: Basic protection parameters
No.
Name
Content
Set value
P0-13
(C00DH)
Fault self-recovery times
ALL
0~20(0 means no automatic reset fault)
Factory default
:
0
Range
:
0~20
P0-14
(C00EH)
Fault self-recovery
interval
ALL
1.0s~100.0s
Factory default
:
10.0s
Range
:
1.0s~100.0s
P0-15
(C00FH)
Relay action selection
when automatic fault
reset
ALL
0: Relay does not operate
1: Relay action
Factory default
:
0
Range
:
0~1
P0-16
(C010H)
Input loss phase detection
filter time
ALL
0.0s~10.0s (0.0s means Not detect)
Factory default
:
5.0s
Range
:
0.0s~10.0s
P0-17
(C011H)
Output loss phase
detection Enable
ALL
0: Invalid
1: Valid
Factory default
:
0
Range
:
0~1
P0-18
(C012H)
Fan control selection
ALL
0: Fan runs when the inverter is in standby
1: Fan not run when the inverter is in standby
Factory default
:
1
Range
:
0~1
P0-19
(C013H)
Short circuit relay
detection Enable
ALL
0: Valid
1: Invalid
Factory default
:
0
Range
:
0~1
Note: <1>: Factory default of 220V series inverter is 360.0V; Factory default of 380V series inverter is
680.0V
For 220V series inverter, the Max. is 360.0V and the Min. is 320.0V, for 380V series inverter, the Max. is
720.0V and the Min. is 640.0.V